What is the minimum distance between two magnetic switches to avoid mutual interactions?
The minimum distances between a magnet and a switch plus a magnet to avoid mutual interactions are
• Schneider XCS-DMP: L>100mm
• Schneider XCS-DMC: L> 40mm
• Schneider XCS-DMR: L> 40mm (or 70mm from diameter 30, axis to axis)
The magnet of another couple disturbs the magnetic field of the first couple switch and magnet. This applies to ATEX switches XCSDMC EX.